|本期目录/Table of Contents|

[1]魏新劳,李林骜,聂洪岩,等.5 0 0 kV电力变压器匝间绝缘模型线圈的电老化特性[J].电机与控制学报,2017,21(03):17-24.[doi:10.15938/j. emc. 2017.03. 003]
 WEI Xin-lao,LI Lin-ao,NIE Hong-yan,et al. Electrical aging characteristic of 500 kV power transformer turn-to-turn insulation model coils [J].,2017,21(03):17-24.[doi:10.15938/j. emc. 2017.03. 003]
点击复制

5 0 0 kV电力变压器匝间绝缘模型线圈的电老化特性(PDF)
分享到:

《电机与控制学报》[ISSN:1007-449X/CN:23-1 408/TM]

卷:
21
期数:
2017年03
页码:
17-24
栏目:
出版日期:
2018-03-15

文章信息/Info

Title:
 Electrical aging characteristic of 500 kV power transformer turn-to-turn insulation model coils


作者:
魏新劳李林骜聂洪岩裴震王永红陈庆国
 (哈尔滨理工大学工程电介质及其应用教育部重点实验室,黑龙江哈尔滨150080)
Author(s):
 WEI Xin-lao LI Lin-ao NIE Hong-yan PEI Zhen WANGYong-hong CHEN Qing-guo
 (MOEKey Laboratory of Engineering Dielectrics and Its Application Harbin University of Science and Technology Harbin 150080, China)








关键词:
500 kV电力变压器电老化匝间绝缘模型线圈电压寿命指数
Keywords:
500kV power transformer electrical aging turn-to-turn insulation model coils voltage endurance coefficient
分类号:
TM 411
DOI:
10.15938/j. emc. 2017.03. 003
文献标志码:
A
摘要:
针对变压器匝间绝缘是电力变压器损坏事故中的主要损坏部位的问题,设计并制作了5 0 0 kV电力变压器匝间绝缘的线圈模型,研究匝间绝缘的电老化特性。根据模型线圈预试验的结果,确定了实验方案,并基于极大似然法思想确定求取反幂模型中的参数方法;最后求取不同数据量下的参数值。分析结果表明:不同数据量下所求得的参数值不同,若使电压寿命指数C不出现异常值,至少需要在4种电压持续时间下进行实验;在1 0种电压持续时间下可得到可靠的电压寿命指数C,其值为1 3.3 8。最终通过简单计算及仿真分析求得了老化寿命与电场强度间的反幂模型,用于指导实际变压器的生产设计。

Abstract:
In order to solve the problem of transformer tum-to-tum insulation is the main positions of pow­er transformer damage accident. 500 kV power transformer tum-to-tum insulation model coils were designed and fabricated to study the electrical aging characteristic of tum-to-tum insulation. By the results of preliminary test of the model coils,the right experimental scheme was selected; then the determined to calculate the parameters of the model of inverse power on the basis of maximum likelihood method;the parameters were calculated under different amount of data. The result of analysis show that different amount of data make parameters calculated different and it needs at least four kinds of time that voltage continue to obtain the right voltage endurance coefficient C,and it was got in a reliable way under 10 kind of time. In this way,the value is 13. 38. Finally,the inverse power model between aging life and electric field strengtli was obtained through the calculation and simulated analysis,which can be used to guide the actual transformer production design.

参考文献/References:

相似文献/References:

备注/Memo

备注/Memo:
收稿日期:2016 -02-15
基金项目:国家重点基础研究发展“973”计划项目(2012CB723308)
作者简介:魏新劳(I960—$,男,博士,教授,博士生导师,研究方向为高电压试验技术和电气设备绝缘检测和诊断;
李林骜(1991—),男,博士研究生,研究方向为电力变压器线圈匝间绝缘电老化;
聂洪岩(1984—),男,博士研究生,讲师,研究方向为高电压试验技术;
裴震(1990—),男,硕士,研究方向为高电压试验技术;
王永红(1972—),男,博士,教授,研究方向为高电压技术;
陈庆国(1970—),男,博士,教授,博士生导师,研究方向为高电压绝缘、高电压应用新技术。